The following diagnostic parameters are supported for each Remote Node connected to the local workstation:
You must use the full path to a parameter on the Remote Operator Station to access the value of that parameter. Path is specified as:
Local Server Name/Remnet/Remote Station Name/parameter
(where Remnet is the required subsystem name)
For example, to access the value of OINTEG on a Remote Operator Station called Cosmos that uses the local server Galileo, the path is:
Galileo/Remnet/Cosmos/OINTEG
The easiest way to find a parameter path is to right-click the parameter in the Contents pane in DeltaV Diagnostics and select Properties. An exception is the channel value, which cannot be accessed directly from Operator Graphics. You must assign the channel value to a module parameter in order to use it on graphics.