A number of parameters hold state information in the switch module. These parameters are not intended to be configurable.
|
Parameter Name |
Parameter Type |
Default Value |
Description |
|---|---|---|---|
|
COMM_ACT |
32-bit unsigned integer1 |
0 |
When non-zero, indicates that the COMM_ALM is active. |
|
FAILED_ACT |
32-bit unsigned integer |
0 |
When non-zero, indicates that the FAILED_ALM is active. |
|
MAINT_ACT |
32-bit unsigned integer |
0 |
When non-zero, indicates that the MAINT_ALM is active. |
|
ADVISE_ACT |
32-bit unsigned integer |
0 |
When non-zero, indicates that the ADVISE_ALM is active. |
|
COMM_P1 |
String |
(empty string) |
Reserved for use by DeltaV software. |
|
FAILED_P1 |
String |
(empty string) |
Reserved for use by DeltaV software. |
|
MAINT_P1 |
String |
(empty string) |
Reserved for use by DeltaV software. |
|
ADVISE_P1 |
String |
(empty string) |
Reserved for use by DeltaV software. |
|
HACACTCNT |
32-bit unsigned integer |
0 |
The number of (unsuppressed) active hardware alarm conditions in the switch. (The number of active conditions shown in the Condition Summary application for this switch.) |
|
HACSUPCNT |
32-bit unsigned integer |
0 |
The number of suppressed hardware alarm conditions in the switch. (The number of suppressed conditions shown in the Condition Summary application for this switch.) |