The valid range of update intervals is 1 through 65 seconds. The fastest recommended update interval is 5 seconds.
If the update interval named range is missing or invalid, the update rate of 10 seconds is used.
If you are creating a workbook with several DeltaV functions, you can reduce the amount of calculations that the workbook performs by putting MS Excel in manual calculation mode.
If a workbook has DeltaV read functions on more than one sheet, the update interval should only be defined on one of the sheets. All of the sheets use the same update interval. In fact, the DeltaV Function Wizard does not allow you to create two update intervals. For example, if the update interval is already defined on Sheet1 and you define a new update interval on Sheet2 with the DeltaV Function Wizard, the DeltaV Function Wizard moves the update interval named range from Sheet 1 to Sheet 2.
If multiple workbooks containing DeltaV functions are open, each workbook must have the update interval defined. For predictable results, all the update intervals should be the same. If the update interval is 5 seconds in each workbook, then updates will occur every 5 seconds in each workbook (assuming data has changed). If there is a different update interval in each workbook, updates will occur at the rate of the active workbook.