Missing values in the Resource or Transducer block could indicate a
database or device error. If any of the necessary parameter values in the
Resource or Transducer block are blank, try:
- Closing and restarting
DeltaV Explorer.
- Power cycling the device by:
- Decommissioning the
device.
- Disconnecting the device
from the segment.
- Waiting 10 –15 seconds
and then reconnect the device.
- For four wire
transmitters such as MicroMotion, disconnect the power source and the segment
connection and reconnect the segment wiring after reconnecting the power source
(usually the AC power source).
- Restarting the device by:
- Right-clicking the
device in DeltaV Explorer. If the device supports a method, select the Restart
option and follow the instructions provided by the wizard.
- If the device does not
support a method:
- Select
- Select the Hardware
tab
- Change Restart to
Processor
- Click Apply