Maximum distances per load on the MTL9112 NI power supply

It is assumed that each device has an average load of 20 mA. If your devices average more than 20 mA per device, reduce the maximum cable length indicated in the table for that number of devices or reduce the number of devices on that segment.

Table: Distance per load on 9112 NI power supply
Number of field devices Power supply load (mA) Maximum distance (meters)
1 20 1900
2 40 1870
3 60 1250
4 80 930
5 100 750
6 120 620
7 140 530
8 160 460
9 180 410
10 200 370
11 220 340
12 240 310
13 260 280
14 280 260
15 300 250
16 320 230
Note

In any hazardous area installation it is important to read and follow the device manufacturer's design and installation documents. Failure to follow the documentation could result in an unapproved and unsafe application. Additionally, in hazardous locations follow your plant's procedures for making the area safe during installation and maintenance operations.