Distance per load on the Fieldbus Power Hub with segment protection

When referring to following table, remember that the H1 card requires 12 mA of fieldbus power in simplex mode and an additional 12 mA of fieldbus power (24 mA total) in redundant mode. The distance associated with the segment protector accounts for the possibility of a short on a spur which would increase the current on the trunk and also reduce the voltage to the other devices.

Table: Distance per load on the Fieldbus Power Hub with Segment Protectors
Number of Devices / Load (mA) Power Supply Load (mA) Maximum distance with Segment Protectors (meters)
H1 Simplex H1 Redundant
1 / 20 32 44 1900
2/ 40 52 64 1900
3 / 60 72 84 1780
4 / 80 92 104 1545
5 / 100 112 124 1370
6 / 120 132 144 1230
7 / 140 152 164 1115
8 / 160 172 184 1015
9 / 180 192 204 935
10 / 200 212 224 870
11 / 220 232 244 810
12 / 240 252 264 755
13 / 260 272 284 710
14 / 280 292 304 670
15 / 300 312 324 635
16 / 320 332 344 605
16 / 340 352 364 575
16 / 360 372 384 545