Maximum distances per load on the H1 with Integrated Power card

This table shows the maximum distance, in meters, for applications that use the H1 with Integrated Power card with short circuit protection. The total distance is reduced to prevent a short on the spur from disrupting the trunk.

Table: Distances per load on the H1 with Integrated Power card
Number of devices Power supply load (mA) Maximum distance with Megablocks (meters)
Redundant H1 with Integrated Power
1 20 1900
2 40 1900
3 60 1900
4 80 1900
5 100 1900
6 120 1900
7 140 1900
8 160 1755
9 180 1605
10 200 1485
11 220 1375
12 240 1285
13 260 1205
14 280 1135
15 300 1070
16 320 1015