| CHARMs
|
ISA-S71.04-1985 Airborne Contaminants Class G3
|
- 1 mm peak-to-peak
from 2 Hz to 13.2 Hz
- 0.7 g from 13.2 Hz
to 150 Hz
|
10 g ½ sine wave for 11 ms
|
| CHARM I/O card
|
ISA-S71.04-1985 Airborne Contaminants Class G3
|
- 1 mm peak-to-peak
from 2 Hz to 13.2 Hz
- 0.7 g from 13.2 Hz
to 150 Hz
|
10 g ½ sine wave for 11 ms
|
| Controllers
|
ISA-S71.04-1985 Airborne Contaminants Class G3
|
- 1 mm peak-to-peak
from 5 Hz to 16 Hz
- 0.5 g from 16 Hz to
150 Hz
|
10 g ½ sine wave for 11 ms
|
| DeltaV Bulk Power Supplies
|
|
5, 10, 20 A models:
- ±1.6 mm from 2-17.8 Hz
- 2 g from 17.8-500 Hz for 2 hours
40 A model:
- ±1.6 mm from 2-17.8 Hz
- 1 g from 17.8-500 Hz for 2 hours
|
5, 10, 20 A models:
- 30 g, 6 ms duration at 3 bumps
- 20 g, 11 ms duration at 3 bumps
40 A model:
- 15 g, 6 ms duration at 3 bumps
- 10 g, 11 ms duration at 3 bumps
|
|
DeltaV Smart Switches and media modules
|
|
- 1 mm , 2 Hz to 13.2
Hz for 90 minutes
- 0.7g, 13.2 Hz to
100 Hz for 90 minutes
- 3.5 mm, 3 Hz to 9
Hz, 10 cycles, 1 octave/minute
- 1g, 9 Hz to 150 Hz,
10 cycles, 1 octave/minute
|
15 g, 11 ms duration at 18 shocks
|
| Ethernet I/O Cards
|
ISA-S71.04-1985 Airborne
Contaminants Class G3
|
- 1 mm peak-to-peak from 2 Hz to 13.2 Hz
- 0.7 g from 13.2 Hz to 150 Hz
|
10 g ½ sine wave for 11 ms
|
| I/O cards
|
ISA-S71.04-1985 Airborne Contaminants Class G3
|
- 1 mm peak-to-peak
from 5 Hz to 16 Hz
- 0.5 g from 16 Hz to
150 Hz
|
10 g ½ sine wave for 11 ms
|
|
System power supply (24 VDC)
|
ISA-S71.04-1985 Airborne Contaminants Class G3
|
- 1 mm peak-to-peak
from 5 Hz to 16 Hz
- 0.5 g from 16 Hz to
150 Hz
|
10 g ½ sine wave for 11 ms
|
| WirelessHART I/O card
|
ISA-S71.04-1985 Airborne Contaminants Class G3
|
- 1 mm peak-to-peak
from 2 Hz to 13.2 Hz
- 0.7 g from 13.2 Hz
to 150 Hz
|
10 g ½ sine wave for 11 ms
|
| Workstation
|
Refer to manufacturer's specifications.
|
Refer to manufacturer's specifications.
|
Refer to manufacturer's specifications.
|