DO 100 mA energy limited CHARM specifications

Installation notes

Specifications

Table: DO 100 mA energy limited CHARM specifications
Item Specification
Channel type Discrete output: 24 VDC high-side
Configuration options
  • Momentary output
  • Continuous pulse output
  • Line fault testing
On-state output rating

24 VDC nominal at 100 mA

Channel power is derived from +24 VDC (± 10%) power supplied to CHARM I/O card.

On-state current limiting, channel protection

Output maximum current: current limited to 107 mA nominal

Off-state leakage current 1 mA maximum
Line fault detection levels
  • Guaranteed short circuit: <50 Ω load
  • Guaranteed good status: 240 Ω to 10 kΩ load
  • Guaranteed open circuit: >20 kΩ load
Line fault test timing 200 µsec
Input power requirements Total power requirement: +24 VDC ±10% at 116 mA maximum :
  • Input power from CIOC: +6.3 VDC ±3% at 32 mA maximum
  • +24 VDC input power: +24 VDC ±10% at 5 mA maximum plus output channel current
CHARM heat dissipation 0.56 W

Wiring diagram

Figure: DO 100 mA energy limited CHARM wiring diagram