This CHARM has short
circuit protection and supports line monitoring for sensing field wiring faults
such as open and short circuits. Line monitoring is enabled in the
configuration.
Note
Line fault detection is not compatible with significant
capacitive loading (cable + load > 30 nF) and must be disabled under these
conditions.
This CHARM can be
configured for momentary output or continuous pulse output.
Specifications
Table: DO 100 mA energy limited CHARM specifications
Item
Specification
Channel type
Discrete output: 24 VDC high-side
Configuration options
Momentary output
Continuous pulse
output
Line fault testing
On-state output rating
24 VDC nominal at 100 mA
Channel power is derived from +24 VDC (± 10%) power supplied
to CHARM I/O card.
On-state current limiting, channel protection
Output maximum current: current limited to 107 mA nominal
Off-state leakage current
1 mA maximum
Line fault detection levels
Guaranteed short
circuit: <50 Ω load
Guaranteed good
status: 240 Ω to 10 kΩ load
Guaranteed open
circuit: >20 kΩ load
Line fault test timing
200 µsec
Input power requirements
Total power requirement: +24 VDC ±10% at 116
mA maximum :
Input power from
CIOC: +6.3 VDC ±3% at 32 mA maximum
+24 VDC input
power: +24 VDC ±10% at 5 mA maximum plus output channel current
CHARM heat dissipation
0.56 W
Wiring diagram
Figure: DO 100 mA energy limited CHARM wiring diagram