The following table describes the LEDs on the simplex S-series AI 16-Channel 4-20 mA HART card and the redundant S-series AI 16-Channel 4-20 mA HART Plus card.
| LED correct operating condition | Fault indication | Possible causes and corrective action |
|---|---|---|
Power/Active On (green)
|
Off | System power is not supplied to the card due to a possible line power problem. Check the power connections. |
| Internal fault. Contact technical support. | ||
| Error-Off | Red (continuous) | |
| No field power. Check field power source and connections. | ||
| Controller is not scanning card. Check controller operation. | ||
| Card failed self-test. Contact technical support. | ||
| Redundant card (red flashing) | No field power. Check field power source and connections and use the DeltaV Diagnostics Clear Saved Fault Information command when the problem is fixed. | |
| Controller is not scanning card. Check controller operation. | ||
| Hardware error. Replace card with card of same type, contact technical support. | ||
| Simplex card (red flashing) | Controller is not scanning card. Check controller operation. |