AI 8-channel 4-20 mA HART card LEDs

Table: AI 8-channel 4-20 mA HART card LEDs
LED correct operating condition Fault indication Possible causes and corrective action
Power/Active-On (green):
  • Continuous green for the active card
  • Flashing green for the standby card
Off System power is not supplied to the card due to a possible line power problem. Check the power connections.
Internal fault. Contact technical support.
Error-Off Red (continuous) No field power. Check field power source and connections.
Controller is not scanning card. Check controller operation.
Card failed a self–test. Contact technical support
Redundant card (red flashing) No field power. Check field power source and connections and use the DeltaV Diagnostics Clear Saved Fault Information command when the problem is fixed.
Controller is not scanning card. Check controller operation.
Hardware error. Replace card with card of same type, contact technical support.
Simplex card (red flashing) Controller is not scanning card. Check controller operation.
Channel 1 to channel 8-On (yellow) Off Input is out of range and the channel is disabled. Check input source and connections and refer to the card’s specifications for the correct input range.
No field power. Check field power source and connections.
Internal fault. Contact technical support
Yellow (flashing) Input is out of range and the channel is disabled. Check input source and connections and refer to the card’s specifications for the correct input range.
No field power. Check field power source and connections.
Channel is configured for HART but there is no HART communications. Check HART input source and connections.
Channel is configured for NAMUR limits and they have been exceeded. Check input levels compared to NAMUR levels.