AO 8-channel 4-20 mA HART card LEDs

Table: AO 8-channel 4-20 mA HART card LEDs
LED correct operating condition Fault indication Possible causes and corrective action
Power/Active–On (green):
  • Continuous green for the active card
  • Flashing green for the standby card
Off System power is not supplied to the card due to possible line power problems. Check the power connections.
Internal fault. Contact technical support.
Error-Off Red (continuous) Card failed self-test. Contact technical support.
Controller is not scanning card. Check controller operation.
Redundant card (red flashing) No field power. Check field power source and connections. Use the DeltaV Diagnostics Clear Saved Fault Information command when the problem is fixed.
Controller is not scanning the card. Check the controller operation.
Hardware error. Replace card with known good card of same type; contact technical support.
Simplex card (red flashing) Controller is not scanning card. Check controller operation.
Channel 1 to Channel 8-On (yellow) Off No output device (load) and channel is disabled. Check output connections.
Field power is not supplied to card. Check field power source and communications.
Internal fault. Contact technical support.
Yellow (flashing) No output device (load) and channel is enabled. Check output connections.
Field power not supplied to the card. Check field power source and connections.
Channel is configured for HART but there is no HART communication. Check HART input source and connections.
Internal fault. Contact technical support.