100-240 VAC to 24 VDC 20 A DeltaV Bulk Power Supply LEDs

Table: LEDs on the 100-240 VAC to 24 VDC 20 A DeltaV Bulk Power Supply
Condition Overload LED DC OK LED DC OK contact
Normal mode Off On Closed
During BonusPower® Off On Closed
Overload (Vout <90%) (1) Off Open
Output short circuit (1) Off Open
Temperature shutdown (1) Off Open
No input power Off Off Open
(1) At up to 4 seconds of overloading, the power supply delivers continuous output current . After 4 seconds, the output power is reduced to nearly zero for approximately 17 seconds before a new start attempt is automatically performed. If the overload is cleared, the device operates normally. If the overload still exists, the output current is delivered for 2 to 4 seconds (depending upon the overload) again followed by a 17 second time out. This cycle is repeated as long as the overload exists. The red overload LED is permanently on when the overload current is continuously flowing. During the 17 second time out, the red LED flashes with a frequency of approximately 1.3 Hz.