| Green (continuous)
|
The channel and CHARM status is good and the
CHARM is configured.
Note If a bad configuration is downloaded to a successfully
configured CHARM, the CHARM rejects the bad configuration and remains
configured with the good configuration. In this case the LED pattern is Green
(continuous).
|
| Green (flashing twice per second)
|
The CHARM has a connected device but is not
configured. If DeltaV Diagnostics displays BAD status for this CHARM, a
configuration error, such as a configuration mismatch has occurred. If DeltaV
Diagnostics displays GOOD status for the CHARM, the CHARM has not been
configured. In this case, configure the CHARM in DeltaV Explorer.
Note This pattern (green LED flashing twice per second) only
occurs if the CHARM is uninstalled and a configuration change is downloaded. If
the CHARM is not uninstalled and a configuration change is downloaded, this
pattern does not occur.
|
| Green (flashing ten times per second)
|
A user has issued an identify CHARM command
from the DeltaV Diagnostics application. This is not a fault and no action is
required.
|
| Red (continuous)
|
No communications on the bus or no address.
- If this pattern is
seen on an individual CHARM, replace the CHARM.
- If this pattern is
seen on a group of 12 CHARMs, ensure that the correct address plug is
installed.
- If this pattern is
seen on all CHARMs, ensure that the CHARM I/O card is functioning correctly.
- If this pattern is
seen on all CHARMs, the CIOC could be in simulate mode. If the CIOC is in
simulate mode, no corrective action is required.
|
| The connectors on the CHARM Column Extenders
are crossed.
|
| Red (flashing twice per second)
|
Channel fault or hardware error. Check wiring
and associated field device. If wiring and device are correct, replace the
CHARM. This pattern can also occur if an unconfigured CHARM with no connected
device is installed onto the baseplate.
|
| Red (flashing ten times per second)
|
Duplicate address. Check all CHARMs
baseplates for a duplicate address plug.
|
| Green then red flashing four times per second
|
A CHARM fault (such as a bad address or a
faulty CHARM bus) exists that does not affect the channel status.
- If this pattern is
seen on an individual CHARM, replace the CHARM.
- If this pattern is
seen on a group of 12 CHARMs, ensure that the correct address plug is
installed.
- If this pattern is
seen on all CHARMs, ensure that the CHARM I/O card is functioning correctly.
|
| Green and red alternating two times per
second
|
The CHARM is being upgraded or is in upgrade
mode.
|
| Green then red flashing briefly once every
1.5 seconds (for output CHARMs only)
|
The CIOC has placed the CHARM in a fault
state.
|
| No colors
|
The CHARM is unpowered or not functioning.
- If all CHARMs'
LEDs are not showing a color, check the power connections.
- If the LEDs on all
the CHARMs on a baseplate are not showing a color, check the connection to the
baseplate.