VIM card LEDs

Table: VIM card LEDs
LED correct operating condition Fault indication Possible causes and corrective action
Power-On (green) Off System power is not supplied to the card due to a possible line power problem. Check the power connections.
Error-Off Red (continuous) Indicates an error condition.
Active - On (green) Off Indicates that the card is not commissioned and not active. Commission the card.
Standby - On (green) for redundant applications; Off for simplex applications Off (for redundant applications) Indicates that the card is not commissioned. Commission the card.
Flashing No configuration.
Pri - (solid yellow) Off Indicates invalid network communications. Check the power connection; power cycle the card, be sure that the controller is downloaded.
Sec - (solid yellow) Off Indicates invalid LocalBus communications. Check the power connection; power cycle the card; be sure that the controller is downloaded.
All except Power flashing; alternating even and odd indicates that a user has issued a ping command from the user interface to visually identifier the controller. N/A N/A