Table: Temperature and Relative Humidity Specifications for DeltaV Devices
Device Operating Temperature Storage Temperature Relative Humidity
Workstation

10°C to 35°C (50°F to 95°F) maximum 10°C (18°F) change per hour

-20°C to 60°C (-4°F to 140°F)

20% to 80%, non-condensing
3Com 3C16700A 8-Port (TP) Unmanaged Hub 0°C to 40°C (32°F to 104°F) -30°C to 60°C (-22°F to 140°F) 0% to 90%, non-condensing
Allied Telesyn switches:
  • AT-FS708 8-Port (TP) Unmanaged
  • AT-FS709FC 8-Port (TP) Unmanaged with 1 100BASE-FX Fiber Port
0°C to 40°C (32°F to 104°F) -25°C to 70°C (-13°F to 158°F) 5% to 95%, non-condensing
Cisco switches:
  • 2940 8-Port (TP) Managed with 1 100BASE-FX Fiber Port
  • 2950 24-Port (TP) Managed
  • 2950C 24-Port (TP) Managed with 2 100BASE-FX Fiber Ports
  • 2960 8-Port (TP) with 1 gigabit multi-function port
  • 2960 24-Port (TP) with 2 RJ45 ports
  • 2960 24-Port (TP) with 2 gigabit multi-function ports
  • 2960 48-Port (TP) with 2 RJ45 ports
  • 2960 48-Port (TP) with 2 gigabit multi-function ports
  • 3550FX 24-Port (FO) Managed with 24 100BASE-FX Fiber Ports and 2 GBIC gigabit slots
  • 3750-24FS 24-Port (FO) Managed with 24 100BASE-FX Fiber Ports and 2 SFP Gigabit slots
  • 3750-24TS-S 24-Port (TP) Managed with 2 SFP Gigabit slots
  • 3750G-12S-S 12 Slot (SFP) Managed
0°C to 45°C (32°F to 113°F) -25°C to 70°C (-13°F to 158°F) 10% to 85% non-condensing
DeltaV MD20 and MD30 base Smart Switches and media modules, and DeltaV FP20 Smart Switches (non ES versions) 0°C to 60°C (32°F to 140°F) -40°C to 85°C (-40°F to 185°F) 10% to 95%, non-condensing
DeltaV MD20 and MD30 base Smart Switches and media modules, and FP20 Smart Switches (ES versions) -40°C to 70°C (conformal coating) (-40°F to 158°F) -40°C to 85°C (-40°F to 185°F) 10% to 95%, non-condensing
DeltaV RM100 Smart Switches 0°C to 50°C (32°F to 122°F) -20°C to 85°C (-4°F to 185°F) 10% to 95%, non-condensing
DeltaV RM104 base Smart Switches and media modules 0°C to 50°C (32°F to 122°F) -20°C to 85°C (-4°F to 185°F) 10% to 95%, noncondensing
MD Plus Controllers -40°C to 70°C (-40°F to 158°F) -40°C to 85°C (-40°F to 185°F) 5% to 95%, non-condensing
MX Controllers -40°C to 60°C (-40°F to 140°F) -40°C to 85°C (-40°F to 185°F) 5% to 95%, non-condensing

Single Port Fiber Switch

Four Port Fiber Switch

Remote Interface Unit

-40°C to 70°C (-40°F to 158°F) -40°C to 85°C (-40°F to 185°F) 5% to 95%, non-condensing
Pre-Series 2 Profibus, Pre-Series 2 DeviceNet 0 to 55°C (32°F to 131°F) -40°C to 85°C (-40°F to 185°F) 5% to 95%, non-condensing
Series 2 I/O (except Series 2 As-Interface) -40°C to 70°C (-40°F to 158°F) -40°C to 85°C (-40°F to 185°F) 5% to 95%, non-condensing
Series 2 As-Interface -25°C to 70°C (-13°F to 158°F) -40°C to 85°C (-40°F to 185°F) 5% to 95%, non-condensing
System power supplies 0 to 60°C (32°F to 140°F) -40°C to 70°C (-40°F to 158°F) 5% to 95%, non-condensing
System Power Supply (Dual DC/DC) -40 to 70°C (-40°F to 158°F) -40°C to 70°C (-40°F to 158°F) 5% to 95%, non-condensing
Legacy DIN rail-mounted bulk power supply -40 to 70°C (-40°F to 158°F) -40°C to 70°C (-40°F to 158°F) 5% to 95%, non-condensing
Legacy Panel-mounted bulk power supply 0 to 60°C (32°F to 140°F) at 300 W and altitude < 914 m (3000 ft) -40°C to 85°C (-40°F to 185°F) 5% to 95%, non-condensing
DeltaV Controller Firewall 0 to 55°C (32°F to 131°F) -40°C to 80°C (-40°F to 176°F)

10% to 95%, non-condensing

Fiber-Optic Media Converter 0 to 60°C (32°F to 140°F) -40°C to 70°C (-40°F to 158°F) 5% to 95%
Fieldbus H1 Carrier -40°C to 70°C (-40°F to 158°F) -40°C to 85°C (-40°F to 185°F) 5% to 95%, non-condensing
Round ribbon cable 0°C to 60°C (0°F to 140°F) -20°C to 70°C (-4°F to 158°F) 5% to 95%, non-condensing
Table: Airborne Contaminants, Vibration, and Shock Specifications for DeltaV Devices
Device Airborne Contaminants Vibration Shock
Workstation Refer to manufacturer’s specifications Refer to manufacturer’s specifications Refer to manufacturer’s specifications
8-port hub Refer to manufacturer’s specifications Refer to manufacturer’s specifications Refer to manufacturer’s specifications
All switches in the preceding table. Refer to manufacturer’s specifications Refer to manufacturer’s specifications Refer to manufacturer’s specifications

Fieldbus H1 carrier, system power supplies, controllers, Single Port Fiber Switch, Remote Interface Unit,

pre-Series 2 I/O, and Series 2 I/O

ISA-S71.04-1985 Airborne Contaminants Class G3

1 mm peak-to-peak from 5 Hz to 16 Hz, 0.5 g from 16 Hz to 150 Hz

10 g ½-sinehalf-sine wave for 11 ms

DeltaV Controller Firewall Refer to manufacturer’s specifications Refer to manufacturer’s specifications Refer to manufacturer’s specifications
Legacy Bulk power supplies ISA-S71.04-1985 Airborne Contaminants Class G2 MIL-STD-810D Method 514.3, Category 1, Procedure I MIL-STD-810D Method 516.3, Procedure III