Checking Out and Troubleshooting Your DeltaV System > Checking Out Your System > Step 3. Checking the LED Indicators on Each Device

AI 16-Channel Card LEDs

The following table describes the LED indicators for the Series 2 AI, 16-Channel, 4-20 mA, HART card in Simplex mode.

Table: AI 16-Channel Card LEDS
LED Correct Operating Condition Fault Indication Possible Cause Corrective Action
Green-Power On Off 1. System power is not supplied to unit. Possible line power problem 1. Check supply power and connections.
2. Internal fault. 2. Contact technical support.
Red - Error Off On 1. No bussed field power. 1. Check bussed field power and connections.
2. Controller is not scanning card. 2. Check controller operation.
3. Unit failed self-test. 3. Contact technical support.
Flashing 1. No bussed field power. 1. Check bussed field power and connections.
2. Controller is not scanning card. 2. Check controller operation.
3. Hardware error. 3. Replace card with known good card of same type; contact technical support.