Green – Power
Green Power/Active
|
- pre-Series 2 - On
- Series 2 Simplex -
On
- Series 2 Redundant:
- Active - On
- Standby -
Flashing
|
Off
|
1. System power is not supplied to unit.
Possible line power problem.
|
1. Check supply power and connections.
|
| 2. Internal fault.
|
2. Contact technical support.
|
| Red-Error
|
Off
|
pre-Series 2 and Series 2 On
(continuous)
|
1. No bussed field power.
|
1. Check bussed field power and connections.
|
| 2. Controller is not scanning card.
|
2. Check controller operation.
|
| 3. Unit failed self-test.
|
3. Contact technical support.
|
| pre- Series 2 Flashing
|
1. Controller is not scanning card.
|
1. Check controller operation.
|
| 2. Address conflict.
|
2. Replace card with known good card of same
type; contact technical support.
|
| Redundant Series 2 Flashing
|
1. No bussed field power.
|
1. Check bussed field power and connections.
Use the DeltaV Diagnostics Clear Saved Fault Information command when problem
fixed.
|
| 2.Controller is not scanning card.
|
2. Check controller operation.
|
| 3. Hardware error.
|
3. Replace card with known good card of same
type; contact technical support.
|
| Simplex Series 2 Flashing
|
Controller is not scanning card.
|
Check controller operation.
|
| Yellow - Ch.1 to Ch. 8
|
On
|
Off
|
1. Input is out of range and channel is
disabled. (See specifications in the "Interface Specifications" section.)
|
1. Check input source and connections.
|
| 2. No bussed field power.
|
2. Check bussed field power and connections.
|
| 3.Internal fault.
|
3. Contact technical support.
|
| Flashing
|
1. Input is out of range and channel is
disabled. (See specifications in the "Interface Specifications" section.)
|
1. Check input source and connections.
|
| 2. No bussed field power.
|
2. Check bussed field power and connections.
|
| 3. Channel is configured for HART, but there is
no HART communication.
|
3. Check HART input source and connections.
|
| 4. Channel is configured for NAMUR limits and
they have been exceeded.
|
4. Check input levels compared to NAMUR limits
|