Green - Power
Green Power/Active
|
- pre-Series 2 - On
- Series 2 Simplex -On
- Series 2 Redundant:
- Active - On
- Standby -
Flashing
|
Off
|
1. System power is not supplied to unit.
Possible line power problem.
|
1. Check supply power and connections.
|
| 2. Internal fault.
|
2. Contact technical support.
|
| Red - Error
|
Off
|
pre-Series 2 and Series 2 On
(continuous)
|
1. Controller is not scanning card.
|
1. Check controller operation.
|
| 2. Unit failed self-test.
|
2. Contact technical support.
|
| pre-Series 2 - Flashing
|
1. Controller is not scanning card.
|
1. Check controller operation.
|
| 2. Address conflict.
|
2. Replace with known good card of same type;
contact technical support.
|
| Series 2 - Flashing
|
1. Controller is not scanning card.
|
1. Check controller operation.
|
| 2. Hardware error.
|
2. Replace card with known good card of same
type; contact technical support.
|
| Yellow - Ch.1 to Ch. 8
|
- On = input >
detection level.
- Off = input <
detection level.
Refer to the "Interface Specifications" section for detection
levels for each DI card type.
|
|
|
|