| Green – Power
|
On
|
Off
|
1. System power is not supplied to unit.
Possible line power problems.
|
1. Check supply power and connections.
|
| 2. Internal fault.
|
2. Contact technical support.
|
| Red – Error
|
Off
|
On (continuous)
|
Unit failed self-test.
|
Contact technical support.
|
| Flashing
|
1. Controller is not scanning card.
|
1. Check controller operation.
|
| 2. Unit failed self-test.
|
2. Contact technical support.
|
| 3. Address conflict.
|
3. Replace card with known good card of same
type; contact technical support.
|
| Yellow – Ch.1 to Ch. 8
|
On
|
Off
|
1. No output device (load).
|
1. Check output connections.
|
| 2. Internal fault.
|
2. Contact technical support.
|
| Flashing
|
1. No output device (load).
|
1. Check output connections.
|
|
|
2. Internal fault.
|
2. Contact technical support.
|
| 3. Card is configured for HART but there is no
HART communication.
|
3. Check HART input source and connections.
|