| Green - Power
|
On
|
Off
|
1. System power is not supplied to unit.
Possible line power problem.
|
1. Check supply power and connections.
|
| 2. Internal fault.
|
2. Contact technical support.
|
| Red - Error
|
Off
|
On (continuous)
|
1. Controller is not scanning card.
|
1. Check controller operation.
|
| 2. Unit failed self-test.
|
2. Contact technical support.
|
| Flashing
|
1. Controller is not scanning card.
|
1. Check controller operation.
|
| 2. Address conflict.
|
2. Replace card with known good card of same
type; contact technical support.
|
| Yellow - Ch.1-Ch.16
|
- On = input >
detection level.
- Off = input <
detection level.
See specifications in Appendix C for detection levels for each
card type.
|
Flashing
|
Line fault detected.
|
Check field wiring.
|
| Running light from Channel 1 - Channel 16 with
Red Error On.
|
No terminal block installed or incorrect
terminal block used.
|
Make sure that the correct terminal block is
installed.
|