Checking Out and Troubleshooting Your DeltaV System > Checking Out Your System > Step 3. Checking the LED Indicators on Each Device

I.S. DO 4-Channel Card LEDs

Table: I.S. DO 4-Channel Card LEDs
LED Correct Operating Condition Fault Indication Possible Cause Corrective Action
Green - Power On Off 1. System power is not supplied to unit. Possible line power problem. 1. Check supply power and connections.
2. Internal fault. 2. Contact technical support.
Red Off On (continuous) 1. Controller is not scanning card. 1. Check controller operation.
2. Unit failed self-test. 2. Contact technical support.
Flashing 1. Controller is not scanning card. 1. Check controller operation.
2. Address conflict. 2. Replace card with known good card of same type; contact technical support.
Yellow - Ch. 1 - Ch. 4 Depends on setpoint and configuration. Flashing Line fault detected. Check field wiring.