Checking Out and Troubleshooting Your DeltaV System > Checking Out Your System > Step 3. Checking the LED Indicators on Each Device

Remote Interface Unit LEDs

The following table describes the LED indicators for the Remote Interface Unit.

Table: Remote Interface Unit LEDs
LED Correct Operating Condition Fault Indication Probable Cause Corrective Action
Green – Power On Off 1. System power is not supplied to unit. Possible line power problem. 1. Check supply power and connections.
2. Internal fault. 2. Contact technical support
Red – Error Off On (continuous) Internal fault. Contact technical support
On for one second followed by all LEDs on for five seconds. Unit went through RESET due to an unrecoverable software error. Contact customer support.
Flashing The Remote Interface Unit is decommissioned. Commission the Remote Interface Unit.
Green – Active On Off 1. Remote Interface Unit is not commissioned. 1. Commission the Remote Interface Unit.
2. Internal fault. 2. Contact technical support.
Flashing Remote Interface Unit is not configured. Download configuration.
Green – Standby Off (Redundancy not supported)
Yellow - Pri. CN Communications attempted and indicator flashing Off – Communications attempted and indicator not flashing. Remote Interface Unit lacks active Ethernet communications on primary Control Network connection. Check primary network cable connections and hub connections.
Yellow - Sec. CN Communications attempted and indicator flashing Off – Communications attempted and indicator not flashing. Remote Interface Unit lacks active Ethernet communications on secondary Control Network connection. Check secondary network cable connections and hub connections.