The VIM 2 card has 6 LEDs. The LEDs can have 3 states: On, Off, or Blink (only used for the VIMNet network communications LED). From top to bottom the LEDs are:
The following table shows the LED pattern when the VIM 2 is decommissioned.
The following table shows the LED pattern when the VIM 2 is commissioned and communicating with both the DeltaV controller and with external devices. Note that if the Active LED is on and the Standby LED is off, the redundancy role is Active. If the Active LED is off and the Standby LED is on the redundancy role is Standby.
| LED | State |
|---|---|
| Active | On |
| Standby | Off |
| Network | On |
| Ctlr Comm | On |
| Power | On |
The following table shows the LED pattern when the VIM 2 is commissioned but not communicating on the LocalBus and there is a VIMNet network error. The redundancy role is Active. If the Standby LED is On and the Active is Off with all other LED states the same, the redundancy role is Standby.
| LED | State | Corrective action |
|---|---|---|
| Active | On | Verify that the DeltaV controller is downloaded. Also verify that the external device configuration has been uploaded to the VIM 2 from the VIMNet Explorer |
| Standby | Off | |
| Network | Blink | |
| Ctlr Comm | Off | |
| Power | On |
The following table shows the LED pattern when the VIM 2 is commissioned and communicating on the LocalBus but there are errors on the VIMNet network. The redundancy role is Active. If the Standby LED is On and the Active is Off with all other LED states the same, the redundancy role is Standby.