DeltaV Controllers and the Remote Interface Unit

Remote Interface Unit

The Remote Interface Unit allows standard DeltaV I/O cards to be installed remotely from the controller. The remote subsystem, consisting of the Remote Interface Unit, system power supply, carriers, and I/O cards, can be located in Zone 2. The Remote Interface Unit communicates with the controller over redundant, Control Network (ethernet) connections.

Specifications

The following table shows specifications for the Remote Interface Unit.

Item Specification
Power requirement (supplied by system power supply through 2-wide power/controller carrier) +3.3 VDC at 500 mA maximum +5 VDC at 200 mA maximum
Fuse protection 3.0 A, non-replaceable fuses
Power dissipation 3.0 W maximum
Mounting On right slot of power/controller carrier

Connections and Dimensions

The Remote Interface Unit mounts in the controller slot of a 2-wide carrier and has redundant ethernet connections to the DeltaV Control Network switch or hub. Connect the primary port to the primary switch or hub and the secondary port to the secondary switch or hub. The primary Control Network connection is capable of 10/100Mbit ethernet while the secondary connection is limited to 10Mbit ethernet.

Figure: Remote Interface Unit Dimensions