Installation Worksheets

Worksheet for Products Using 12 V LocalBus Power and 24 VDC Bussed Field Power

Use this table to calculate the power requirements for products that use 12 VDC LocalBus power and 24 VDC bussed field power.

Table: Worksheet for Products Using 12 V LocalBus Power and 24 VDC Bussed Field Power
Product Type Quantity Curent Required for Each Product (A) Total for Product Type
12 VDC LocalBus Power 24 VDC Bussed Field Power 12 VDC 24 VDC

Controllers

0.0(1)

0.0(1)

Remote Interface Unit

0.0(1)

0.0(1)

I/O Cards

AI, 8-Channel, 4-20 mA

0.150

0.300

AI, 8-Channel, 4-20 mA, HART

0.150

0.300

AI, 8-Channel, 1-5 VDC

0.150

0.100

AO, 8-Channel, 4-20 mA

0.150

0.300

AO, 8-Channel, 4-20 mA, HART

0.150

0.300

AS-Interface

0.300

N/A

DeviceNet

0.600

N/A

DI, 8-Channel, 24 VDC, Isolated

0.100

N/A

DI, 8-Channel, 24 VDC, Dry Contact

0.100

0.040

DI, 8-Channel, 120 VAC, Isolated

0.100

N/A

DI, 8-Channel, 120 VAC, Dry Contact

0.100

N/A

DI, 8-Channel, 230 VAC, Isolated

0.100

N/A

DI, 8-Channel, 230 VAC, Dry Contact

0.100

N/A

DI, 32-Channel, 24 VDC, Dry Contact

0.075

0.150

DO, 8-Channel, 120/230 VAC, Isolated

0.150

N/A

DO, 8-Channel, 120/230 VAC, High Side

0.150

N/A

DO, 8-Channel, 24 VDC, Isolated

0.150

N/A

DO, 8-Channel, 24 VDC, High Side

0.150

depends upon field devices (max 3 A total each card)

DO, 32-Channel, 24 VDC, High-Side

0.150

depends upon field devices (max 3.2 A total each card)

Fieldbus H1 card

0.600

N/A

Media Converter

0.300

N/A

Multifunction

0.250

N/A

Profibus DP

0.600

N/A

RTD, ohms

0.160

N/A

Sequence of Events

0.075

0.075

Serial Card, 2 Ports, RS232/RS485

0.300

N/A

Thermocouple, mV

0.350

N/A

Series 2 I/O Cards (2)

Series 2 AI, 4-20 mA with HART

Simplex: 0.150

Redundant: 0.250 (each card)

Simplex: 0.300

Redundant: 0.200 (each card)

Series 2 AI, 16-Channel, 4-20 mA, HART Simplex

0.150

0.600

Series 2 AO, 4-20 mA with HART

Simplex: 0.150

Redundant: 0.250 (each card)

Simplex: 0.300

Redundant: 0.200 (each card)

Series 2 AS-Interface Simplex

0.300

N/A

Series 2 DI, 8-Channel, 24 VDC Dry Contact

Simplex: 0.150

Redundant: 0.150 (each card)

Simplex: 0.040

Redundant: 0.020 (each card)

Series 2 DI, 8-Channel, 24 VDC Isolated Simplex

0.100

N/A

Series 2 DI, 8-Channel, 120 VAC, Dry Contact Simplex

0.100

N/A

Series 2 DI, 8-Channel, 120 VAC Isolated Simplex

0.100

N/A

Series 2 DI, 32-Channel, 24 VDC, Dry Contact Simplex

0.075

0.150

Series 2 DO, 8-Channel, 24 VDC, High-Side

Simplex: 0.150

Redundant: 0.150 (each card)

Simplex: depends upon field devices; (max 3 A total each card)

Redundant: depends upon field devices; (max 1.5 A each card)

Series 2 DO, 8-Channel, 24 VDC Isolated Simplex

0.150

N/A

Series 2 DO, 8-Channel, 120/230 VAC High Side Simplex

0.150

N/A

Series 2 DO, 8-Channel, 120/230 VAC, Isolated Simplex

0.150

N/A

Series 2 DO, 32-Channel, 24 VDC, High-Side Simplex

0.150

depends upon field devices

(max 3.2 A total each card)

Series 2 H1

Simplex: 0.300

Redundant: 0.300 (each card)

N/A

N/A

Series 2 Isolated Input

0.350

N/A

Series 2 DeviceNet

0.600

N/A

Series 2 Profibus DP

0.600

N/A

Series 2 Thermocouple

0.210

Series 2 Sequence of Events Simplex

0.100

0.075

Series 2 Serial

Simplex: 0.300

Redundant: 0.300 (each card)

N/A

N/A

Subtotal 1
(1) Require no LocalBus current as controllers are powered separately by the system power supply.
(2) For Series 2 cards in redundant applications, the numbers shown in the table are for each card of a redundant pair. For example, the power required for a redundant pair of Series 2 DO cards is .300 A at 12 VDC and a maximum of 3 A at 24 VDC for 24 VDC field power.