The DeltaV PK controller must be unlocked to commission, decommission, download, upgrade, or access the node's privileged menus (for example, Telnet access). Locking also prevents a user-initiated switchover when the controllers are redundant. You lock and unlock the controller (when the controller is in one of the Unlock Allow states) in DeltaV Explorer through the controller's context (right-click) menu.
The physical key switch on the controller's carrier can be used to control the software Lock and Unlock functions. The key switch requires physical presence by plant personnel before the controller's locked state can be altered and therefore before any functions controlled by the locked state can be initiated.
This is the shown as the locked symbol on the carrier. When it this position, the controller cannot be unlocked in DeltaV Explorer. Because the controller is locked, you cannot perform certain functions (such as downloading, commissioning, upgrading, and so on). The Unlock Inhibit position is the default operating position when the Enable Unlock Inhibit Key Switch option is enabled.
Enable or disable the physical key switch with the Enable Unlock Inhibit Key Switch option on the controller's Properties dialog's Security tab.
The Unlock Inhibit Key Switch must be enabled (and the physical key switch must be switched into the unlocked position) for the unlock states to become active.
The following are the valid states for the controller's KeyLockStatus diagnostic parameter (viewed in DeltaV Diagnostics by selecting the controller from the hierarchy).
You can set limits and alerts for the controller's locked state. These options are set on the controller's Properties dialog's Security tab