Green - Power
Green Power/Active
|
- pre-Series 2 - On
- Series 2 Simplex -
On
- Series 2 Redundant
- Active - On
- Standby -
Flashing
|
Off
|
1. System power is not supplied to unit.
Possible line power problem.
|
1. Check supply power and connections.
|
| 2. Internal fault.
|
2. Contact technical support.
|
| Red - Error
|
Off
|
pre-Series 2 and Series 2 - On
(continuous)
|
1. Controller is not scanning card.
|
1. Check controller operation.
|
| 2. Unit failed self-test.
|
2. Contact technical support.
|
| pre-Series 2 Flashing
|
1. Controller is not scanning card.
|
1. Check controller operation.
|
| 2. Address conflict.
|
2. Replace card with known good card of same
type; contact technical support.
|
| Series 2 Flashing
|
1. Controller is not scanning card.
|
1. Check controller operation.
|
| 2. Hardware error.
|
2. Replace card with known good card of same
type; contact technical support.
|
| Yellow - Port 1 and Port 2
(configured as Master)
|
On
|
Off
|
No communications.
|
Check connections, cable, and external device.
|
| Flashing
|
Communications error on this port.
|
Check connections, cable, and external device.
|
| Yellow - Port 1 and Port 2 (configured as
Slave)
|
- On - Communicating
- Off - No
communication
- Flashing -
Intermittent communication
|
|
|
|