Environmental Specifications

Environmental Specifications for P-series controller

The following tables list the environmental specifications for normal operation of DeltaV system devices: The first table lists temperature and relative humidity specifications and the second lists airborne contaminants, vibration, and shock specifications

Table: Temperature and Relative Humidity Specifications for DeltaV Devices
Device Operating Temperature Storage Temperature Relative Humidity
PK controller -40°C to +60°C (-40°F to 140°F) -40°C to 85°C (-40°F to 185°F) 5% to 95%, non-condensing
P-series carrier -40°C to 70°C (-40°F to 158°F) -40°C to 85°C (-40°F to 185°F) 5% to 95%, non-condensing
P-series power supply module -40°C to 70°C (-40°F to 158°F) -40°C to 85°C (-40°F to 185°F) 5% to 95%, non-condensing
Workstation

10°C to 35°C (50°F to 95°F) maximum 10°C (18°F) change per hour

-20°C to 60°C (-4°F to 140°F)

20% to 80%, non-condensing
Series 2 I/O (except Series 2 As-Interface) -40°C to 70°C (-40°F to 158°F) -40°C to 85°C (-40°F to 185°F) 5% to 95%, non-condensing
Series 2 As-Interface -25°C to 70°C (-13°F to 158°F) -40°C to 85°C (-40°F to 185°F) 5% to 95%, non-condensing
System power supplies 0 to 60°C (32°F to 140°F) -40°C to 70°C (-40°F to 158°F) 5% to 95%, non-condensing
Fiber-Optic Media Converter 0 to 60°C (32°F to 140°F) -40°C to 70°C (-40°F to 158°F) 5% to 95%
Fieldbus H1 Carrier -40°C to 70°C (-40°F to 158°F) -40°C to 85°C (-40°F to 185°F) 5% to 95%, non-condensing
Round ribbon cable 0°C to 60°C (0°F to 140°F) -20°C to 70°C (-4°F to 158°F) 5% to 95%, non-condensing
Table: P-series Ingress Protection and electromagnetic compatibility
Device Ingress Protection (IP) Electromagnetic Compatibility
PK controller IP 20 Per EN 61326-3-1 (CE), EN 61326-3-2 NE21 (NAMUR) & IACS E10 (Marine)
P-series carrier IP 20 Per EN 61326-3-1 (CE), EN 61326-3-2 NE21 (NAMUR) & IACS E10 (Marine)
P-series power supply module IP 20 Per EN 61326-3-1 (CE), EN 61326-3-2 NE21 (NAMUR) & IACS E10 (Marine)
Table: Airborne Contaminants, Vibration, and Shock Specifications for DeltaV Devices
Device Airborne Contaminants Vibration Shock
PK controller Severity Level G3 (conformal coating used) 1 mm peak-to-peak from 2 to 13.2 Hz; 0.7 g from 13.2 to 150 Hz. 10 g half- sine wave for 11 ms
P-series carrier Severity Level G3 (conformal coating used) 1 mm peak-to-peak from 2 to 13.2 Hz; 0.7 g from 13.2 to 150 Hz. 10 g half- sine wave for 11 ms
P-series power supply module Severity Level G3 (conformal coating used) 1 mm peak-to-peak from 2 to 13.2 Hz; 0.7 g from 13.2 to 150 Hz. 10 g half- sine wave for 11 ms
Workstation Refer to manufacturer’s specifications Refer to manufacturer’s specifications Refer to manufacturer’s specifications
All switches Refer to manufacturer’s specifications Refer to manufacturer’s specifications Refer to manufacturer’s specifications

Fieldbus H1 carrier, system power supplies, controllers, Single Port Fiber Switch, pre-Series 2 I/O, and Series 2 I/O

ISA-S71.04-1985 Airborne Contaminants Class G3

1 mm peak-to-peak from 5 Hz to 16 Hz, 0.5 g from 16 Hz to 150 Hz

10 g ½-sinehalf-sine wave for 11 ms

DeltaV Controller Firewall Refer to manufacturer’s specifications Refer to manufacturer’s specifications Refer to manufacturer’s specifications