Temperature and humidity specifications for CSLS SIS hardware

Device

Operating temperature range

Storage temperature range

Relative humidity

CSLS

-40°C to 70°C (-40°F to 158°F)

-40°C to 85°C (-40°F to 185°F)

5 to 95% non-condensing

CSLS carrier

-40°C to 70°C (-40°F to 158°F)

-40°C to 85°C (-40°F to 185°F)

5 to 95% non-condensing

CSLS Power Module

-40°C to 70°C (-40°F to 158°F)

-40°C to 85°C (-40°F to 185°F)

5 to 95% non-condensing

LS CHARMs

-40°C to 70°C (-40°F to 158°F)(1)

-40°C to 85°C (-40°F to 185°F)

5 to 95% non-condensing

LSN20 safety switches
  • LSN20-6TX2TX
  • LSN20-6TX2MM
  • LSN20-6TX2SM

0°C to 60°C (32°F to 140°F)

-40°C to 70°C (-40°F to 158°F)

10 to 95%

LSN20-6TX2TX-ES

LSN20-6TX2MM-ES

LSN20-6TX2SM-ES

-40°C to 70°C (-40°F to 158°F)

-40°C to 70°C (-40°F to 158°F)

10 to 95%

LS terminal blocks

-40°C to 70°C (-40°F to 158°F)

-40°C to 85°C (-40°F to 185°F)

5 to 95% non-condensing

Dual Universal Safety Carrier

-40°C to 70°C (-40°F to 158°F)

-40°C to 85°C (-40°F to 185°F)

5 to 95% non-condensing

Ethernet Isolation Ports

-40°C to 70°C (-40°F to 158°F)

-40°C to 85°C (-40°F to 185°F)

5 to 95% non-condensing

Local Safety Network Bridge

-40°C to 70°C (-40°F to 158°F)

-40°C to 85°C (-40°F to 185°F)

5 to 95% non-condensing

Safety Network Ports

-40°C to 70°C (-40°F to 158°F)

-40°C to 85°C (-40°F to 185°F)

5 to 95% non-condensing

SRM100 safety switch

0°C to 50°C (32°F to 122°F)

-20°C to 85°C (-4°F to 185°F)

10 to 95%

SZ Controller

-40°C to 70°C (-40°F to 158°F)

-40°C to 85°C (-40°F to 185°F)

5 to 95% non-condensing

SZ Controller carrier

-40°C to 70°C (-40°F to 158°F)

-40°C to 85°C (-40°F to 185°F)

5 to 95% non-condensing

(1) LS DI 120 VAC CHARM has an operating temperature range of -40°C to 60°C (-40°F to 140°F)