CSLS SIS hardware consists of:
- CHARMs Smart Logic Solvers (CSLS)
- CSLS process LS CHARM signals and run the SIS modules that contain
the safety system logic. Redundant CSLS can support up to 96 LS CHARMs. The
maximum number of LS CHARMs (96) are organized in eight banks of 12 LS CHARMs.
Each bank of 12 LS CHARMs is held by a CHARM Baseplate. CSLS mount on CHARMs
Smart Logic Solver Carriers and connect to the Local Safety Network through
connectors on the carriers.
- SZ Controllers
- SZ Controllers mount on either the SZ Controller Carrier or the
Dual Universal Safety Carrier and connect to the Area Control Network and the
Local Safety Network through ports on the carrier. SZ Controllers isolate CSLS
from the rest of the system. SZ controllers receive redundant 24 VDC input
through the carrier. Redundant Modbus TCP ports on the carrier enable an SZ
controller to support standalone SIS installations.
- Local Safety Network Bridges
- Local Safety Network Bridges (LSNB) connect Local Safety Networks
under different SZ Controllers so that secure parameters can be passed between
CHARMs Smart Logic Solvers on different Local Safety Networks. Local Safety
Network Bridges mount on Dual Universal Safety Carriers that house redundant
connections to the Local Safety Network and to the Global
Safety Network.
- CHARMs Smart Logic Solver Carriers
- CSLS Carriers are vertical DIN rail-mounted carriers that hold
redundant CSLS and Power Modules. The CSLS Carrier provides 24 VDC input to the
CSLS and to the Power Modules. The Power Modules provide 6.3 VDC to the LS
CHARMs. The CSLS Carrier houses primary and secondary Safety Network Ports for
connections to the Local Safety Network and a keylock switch that restricts how
and when the CSLS can be unlocked for downloads and upgrades.
- Dual Universal Safety Carriers
- Dual Universal Safety Carriers are horizontal DIN rail-mounted
carriers that hold redundant Local Safety Network Bridges or SZ Controllers.
The Dual Universal Safety Carrier houses primary and secondary Ethernet
Isolation Ports for connections to the
Global Safety Network and
Local Safety Network when used with Local Safety Network Bridges
and connections to the DeltaV Area Control Network and the Local Safety Network
when used with SZ Controllers.
- SZ Controller Carriers
- SZ Controller Carriers are vertical DIN rail-mounted carriers that
hold redundant SZ Controllers. The SZ Controller Carrier houses primary and
secondary Ethernet Isolation Ports for connections to the DeltaV Area Control
Network and to the Local Safety Network.
- Baseplates
- CHARM Baseplates hold Logic Solver CHARMs (LS CHARMs) and I.S.
Baseplates hold LS Intrinsically Safe CHARMs. The baseplates connect to the
CSLS Carrier and to other baseplates through connectors on the baseplates. Each
baseplate holds up to 12 terminal blocks that hold LS CHARMs, and an Address
Plug that determines the address of the baseplate and the CHARMs installed on
the baseplate.
- Logic Solver (LS) CHARMs
- LS CHARMs are single I/O channels that plug into the CHARM Terminal
Blocks on the CHARM Baseplate. The DeltaV system supports analog input,
discrete input, discrete output (including LS DO redundant DTA and LS DO
redundant ETA CHARMs), LS DVC HART simplex and redundant DTA, LS power output,
LS thermocouple input, LS RTD / Resistance Input, and LS voltage CHARMs as well
as LS Intrinsically Safe analog input, discrete input, RTD/ Resistance input,
and Thermocouple / mV input CHARMs.