In a CSLS SIS system, communication occurs over the DeltaV Area Control Network and a Local Safety Network.
The Local Safety Network must be treated as a dedicated standalone Local Area Network (LAN) and must not be connected to any other network including other DeltaV Local Safety Networks. Only DeltaV Safety Switches (LSN20 and SRM100) and DeltaV SIS nodes are supported on the Local Safety Network.