DeltaV system summary > Commissioned devices summary

Primary network summary for commissioned devices

This is a list of summary information for each commissioned device (switch or firewall) in the Primary network.

Column Description
Name The name of the device and its associated module. If the device is not associated with a module or not communicating with its module, the device's IP address appears.
COMM An icon indicates if the device has an active COMM alarm1.
FAILED An icon indicates if the device has an active FAILED alarm1.
MAINT An icon indicates if the device has an active MAINT alarm1.
ADVISE An icon indicates if the device has an active ADVISE alarm1.
Locking Status Shows whether the device is locked or not. If the device is not communicating, ??? appears.
Lock Timer Shows the amount of time left (in minutes) before auto-lockdown. If the Lock Timer cannot be read, ??? appears.
Description The location description of the device configured in the module.
1 No icon indicates no alarm.

Available Commands

The following commands are available from the context menu when a device is selected. Only commands that are applicable to the selected device.

Command Effect
Lock Locks the selected device.
Unlock Unlocks the selected device.
Open Condition Summary Viewer Launches the DeltaV Condition Summary Viewer for the selected device. This menu item is disabled for commissioned devices whose control modules are missing or not communicating.
Flash LEDs Flashes the LEDs on the selected device.
Show advanced switch information Opens the Advanced Switch Information dialog for the selected device.
Telnet to Switch Opens a Telnet session to the device.
SSH to Switch Opens a secure shell (SSH) to the switch's command line interface (CLI).
Change Smart Switch (or Smart Firewall) Management Password Prompts you to enter a new management password for the device.
Upgrade Firmware Initiates a device firmware upgrade.
Restore Defaults Restores the default settings on the selected device.