Metso Automation Intelligent Safety Solenoid with PST - VG9000F, Rev 3 valid engineering units and channel values

MDO Block: Valid Engineering Units and CHANNEL Values

Allows to start and cancel PST test

CHANNEL = 1

IN_D1=PST_START
IN_D2=PST_CANCEL
IN_D3=Test permission
IN_D4=Setpoint

MDI Block: Valid Engineering Units and CHANNEL Values

Provides device status and limit switch information based on physical switches

Channel = 11

Provides device status and open/close binary information based on position measurement

Channel = 12

OUT_D1=Test_STATUS OUT_D1= Test_STATUS
OUT_D2=Failed OUT_D2= Failed
OUT_D3=Open_LS OUT_D3= Open_pos_sensor
OUT_D4=Closed_LS OUT_D4= Closed_pos_sensor
OUT_D5= Maintenance OUT_D5= Maintenance
OUT_D6= Off spec. OUT_D6= Off spec.
OUT_D7= Check func. OUT_D7= Check func

AI Block: Valid Engineering Units and CHANNEL Values

Valve Position

Channel = 21

1342 (%)