Limitorque MX100, Rev 1 valid engineering units and channel values

AI Block: Valid Engineering Units and CHANNEL Values

AI Position

CHANNEL = 12

AI Analog Input 1

CHANNEL = 13

AI Analog Input 2

CHANNEL = 14

%

%

%

DO Block: Valid CHANNEL Values, Block Field Values, and States

DO Control Valve Flow

CHANNEL = 9

DO Network ESD

CHANNEL = 10

DO Relay

CHANNEL = 11

0 = Stop

0 = Disable Network ESD

AS-1 to AS-4 = Bits 0-3

1 = Open

1 = Enable Network ESD

AR-1 to AR-3 = Bits 4-6

2 = Close

   

DI Block: Valid CHANNEL Values, Block Field Values, and States

DI Position & Bus Mode

CHANNEL = 2

DI Position

CHANNEL = 3

DI Actuator Faults 1

CHANNEL = 4

Opened + Remote = 33

Opened = 1

Monitor Relay = 1

Closed + Remote = 34

Closed = 2

Valve Jammed = 2

Opening + Remote = 36

Opening = 4

Manual Moved = 4

Closing + Remote = 38

Closing = 8

Over Torque = 8

Stopped + Remote = 40

Stopped = 16

Phase Error = 16

Opened + Local = 65

 

Over Temp = 32

Closed + Local = 66

 

Monitor Relay +Valve Jammed = 3

Opening + Local = 68

 

Monitor Relay + Manual Move = 5

Closing + Local = 72

 

Monitor Relay + Over Torque = 9

Stopped + Local = 74

 

Monitor Relay + Phase Error = 17

Opened + Stopped = 75

 

Monitor Relay + Over Temp = 33

Closed + Stopped = 76

 

Monitor Relay + Valve Jammed + Manual Move = 7

Opening + Stopped = 78

 

Monitor Relay + Valve Jammed + Phase Error = 19

Closing + Stopped = 82

 

Monitor Relay + Valve Jammed + Over Temp = 35

Stopped + Stopped = 144

   

DI Actuator Faults 2

CHANNEL = 5

DI Actuator Alarms

CHANNEL = 6

DI User Discrete Inputs

CHANNEL = 7

Thermal Overload = 1

Local ESD Active = 1

ESD Input = Bit 0 (Terminal 21)

Phase Error = 2

Remote ESD Active = 2

Open Inhibit = Bit 1 (Terminal 10)

Valve Jammed = 4

Open Inhibit Active = 4

Close Inhibit = Bit 2 (Terminal 9)

Manual Moved = 8

Close Inhibit Active = 8

Stop Pushbutton Input = Bit 3 (Terminal 6)

Open Torque Switch Fault = 16

Local ESD Active + Open Inhibit = 5

Open Pushbutton Input = Bit 4 (Terminal 7)

Close Torque Switch Fault = 32

Local ESD Active + Close Inhibit = 9

Close Pushbutton Input = Bit 5 (Terminal 5)

Thermal Overload + Manual Moved = 9

Remote ESD Active + Open Inhibit = 6

 

Thermal Overload + Phase Error = 3

Remote ESD Active + Close Inhibit = 10

 

Thermal Overload + Valve Jammed = 5

Open Inhibit Active + Close Inhibit Active = 12

 

Open Torque Switch Fault + Manual Moved = 24

   

Close Torque Switch Fault + Manual Moved = 40

   

DI Read Discrete Outputs

CHANNEL = 8

   

State of AS-1 = Bit 0 (Terminals 1,2)

   

State of AS-2 = Bit 1 (Terminals 3,4)

   

State of AS-3 = Bit 2 (Terminals 31,32)

   

State of AS-4 = Bit 3 (Terminals 42,43)