Westlock BIFFIICON2000, Rev 1 valid channel values

AO Block: Valid Units and CHANNEL Values

Position - target

CHANNEL = 40

%

AI Block: Valid Units and CHANNEL Values

Position - actual

CHANNEL = 41

Torque -actual

CHANNEL = 42

%

ft-lb

 

N-m

DO Block: Valid CHANNEL Values, Block Field Values, and States

DO CHANNELs

Description

1 - Open/Close/Stop

0 - Close command

1 - Open command

2 - Stop command

2 - Disable Setpoint and Opne/Close/Stop or allow setpoint to take precedence

0 - Disable Setpoint and send a Close command

1 - Disable Setpoint and send an Open command

2 - Disable Setpoint and send a Stop command

3 - Allow the Setpoint to take precedence

3 - ESD

0 - No ESD command

1 - ESD command

4 - Interlock Open

0 - No Interlock Open command

1 - Interlock Open command

5 - Interlock Close

0 - No Interlock Close command

1 - Interlock Close command

6 - Interlock Close and Open

0 - No Interlock Close and Open command

1 - Interlock Close and Open command

7 - Disable Setpoint and send Open

0 - No Disable Setpoint and send an Open command

1 - Disable Setpoint and send an Open command

8 - Disable Setpoint and send Close

0 - No Disable Setpoint and send a Close command

1 - Disable Setpoint and send a Close command

9 - Disable Setpoint and send Stop

0 - No Disable Setpoint and send a Stop command

1 - Disable Setpoint and send a Stop command

10 - Open

0 - No Open command

1 - Open command

11 - Close

0 - No Close command

1 - Open command

12 - Stop

0 - No Stop command

1 - Stop command

45 - Open/Close

0 - Open command

1 - Close command

DI Block: Valid CHANNEL Values, Block Field Values, and States

DI CHANNELs

Description

14 - Open/Close/Stop

0 - Valve in fully closed position

1 - Valve in fully open position

2 - Valve stopped in an intermediate position

15 - Stop

0 - Inactive

1 - Valve stopped in an intermediate position

16 - Out of FF Control

0 - Actuator in FF control

1 - Actuator not in FF control

17 - Fully Open

0 - Inactive

1 - Valve in fully open position

18 - Fully Closed

0 - Inactive

1 - Valve in fully closed position