Westlock FPAC Valve Controller EL40106, Rev 1 valid channel values

DO Block: Valid CHANNEL Values, Block Field Values, and States

CHANNEL No.

Output (Readback)

1 - Open/Close

0 - Closed

1 - Opened

2 - Closing

3 - Opening

2 - Close

0 - Not Closed

1- Closed

3 - Open

0 - Not Open

1 - Opened

4 - Stop

0 - Not Stopped

1 - Stopped

5 - Open/Close/Stop

0 - Closed

1 - Opened

2 - Stopped

3 - Closing

4 - Opening

6 - Open/Close For Second Valve

0 - Closed 2

1 - Opened 2

2 - Closing 2

3 - Opening 2

7 - Open For Second Valve

0 - Not Closed 2

1 - Closed 2

8 - Close For Second Valve

0 - Not Open 2

1 - Opened 2

DI Block: Valid CHANNEL Values, Block Field Values, and States

CHANNEL No.

Input

9 - Open/Close

0 - Closed

1 - Opened

2 - Stopped

3 - Closing

4 - Opening

10 - Open

0 - Not Open

1- Open

11 - Closed

0 - Not Closed

1 - Closed

12 - Open/Close/Stop

0 - Closed

1 - Opened

2 - Stopped

3 - Closing

4 - Opening

13 - Maskable Signal

0 - Maskable Signals Items OK

1 - One or more Maskable Signal Items has Exceeded limit

14 - Auxiliary Input 1

0 - Auxiliary 1 Dry Contact closed

1 - Auxiliary 1 Dry contact open.

15 - Auxiliary Input 2

0 - Auxiliary 2 Dry Contact closed

1 - Auxiliary 2 Dry contact open.

16 - Open/Close For Second Valve

0 - Closed 2

1 - Opened 2

2 - Stopped 2

3 - Closing 2

4 - Opening 2

17 - Open For Second Valve

0 - Not Open 2

1 - Open 2

18 - Close For Second Valve

0 - Not Closed 2

1 - Close 2