If the I/O Gateway contains redundant Scanner Modules, those
Scanner Modules are now updated to the new firmware without affecting any
running process. Additionally, I/O Blocks under the I/O Gateway that contain
redundant Scanner Modules are also upgraded to the new firmware version.
However, provisioned I/O Blocks that contain simplex Scanner Modules
are not upgraded because doing so could interrupt running
processes.
Important: If the I/O Gateway contains a simplex Scanner
module, the utility displays the warning
Partner Not Present. If you click
Yes on this warning dialog, any running process
will be affected. To avoid interrupting a running process,
click
No. You will need to use DeltaV Diagnostics to identify and
upgrade provisioned simplex Scanner Modules.