| Power-On (green) |
Off |
System power is not supplied to unit. Check power supply and input power connections. |
| Internal fault. Contact technical support. |
| Error-Off (red) |
On (continuous) |
Internal fault. Contact technical support. |
| On for one second followed by all LEDs on for five seconds. |
Unit went through a reset due to an unrecoverable software error. Contact technical support. |
| Flashing |
The CPU is decommissioned. Commission the CPU. |
| Primary control network-flashing (yellow) |
Off |
CPU lacks active Ethernet communications on the primary control network. Check the primary control network's fiber and cable connections. |
| Secondary control network-flashing (yellow) |
Off |