The FAIL_SAFE step includes several actions to put the valves and motor in CAS mode before closing. When configuring these actions in the expression editor, you need to type in ".TARGET" as part of the expression.
| Steps | Action Text | Qualifier |
|---|---|---|
| HOLDING_STATE | A1: '^/FAIL_MONITOR/AGIT_STOPPED/DISABLE.CV' := 1 | |
| A2: '^/FAIL_MONITOR/BASE_IN_OPEN/DISABLE.CV' := 1 | ||
| A3: '^/FAIL_MONITOR/COLOR_IN_OPEN/DISABLE.CV' := 1 | ||
| A4: '^/FAIL_MONITOR/OUTLET_NOT_CLSD/DISABLE.CV' := 1 | ||
| FAIL_SAFE | A1: '//#BLENDER_OUT_1#/A_COMMAND' := 'outlet_state:Closed' | |
| A2: '//#COLOR_IN_VLV#/DC1/MODE.TARGET' := CAS | ||
| A3: '//#COLOR_IN_VLV#/VALVE_SP' := 'vlvnc-sp: CLOSE' | ||
| A4: '//#BASE_IN_VLV#/DC1/MODE.TARGET' := CAS | ||
| A5: '//#BASE_IN_VLV#/VALVE_SP' := 'vlvnc-sp: CLOSE' | ||
| A6: '//#BLENDER_OUT_1#/OUT_PUMP/DC_MODE' := CAS | ||
| A7: \'//#BLENDER_OUT_1#/OUT_PUMP/CAS_SP' := 'mtr2-sp:STOP' | ||
| A8: '//#AGITATOR#/CAS_SP' := 'mtr2-sp : STOP' | ||
| STOP_AGIT | A1: '//#AGITATOR#/CAS_SP' := 'mtr2-sp : STOP' | Delay=2 |