Open the DeltaV Explorer and navigate to the Assigned Recipes object under the Batch Executive.
Make sure that OP_FINISH has been assigned to this Batch Executive so we can select it from the available list of recipes in the Batch Operator Interface.
Stop the Batch Executive (if running).
Download the controller or workstation.
This will download all changes to the phases.
Start the Batch Executive and verify phases.
Open DeltaV Operate to the Process picture.
If there is not any level in the blender, you may need to run the CHG_BASE phase.
Make sure all the valves are closed.
Open the Batch Operator Interface.
Click Add Batch, and then select OP_FINISH from the list of recipes assigned to the Batch Executive. Bind to the Blender UM_BLEND_500.
Select the batch, and then click the Start button.
When the DRAIN phase starts, the Unacknowledged Operator Prompts button in the button bar starts to flash.
Click the Unacknowledged Operator Prompts button.
A new screen opens with a list of unacknowledged operator messages (which should only contain one message).
Double-click the message line to open a dialog to enter a response to the Send this batch to Product (YES) or Waste (NO)? message.
Select Yes.
After another prompt appears to ask the number of gallons to drain, type the number of gallons you want to drain.
Make sure that this number is less than or equal to the level in the blender.
At this point, you may want to go to the Process picture to watch the draining of the blender.
If the blender is not empty, you can run OP_FINISH again and send the rest of the batch to waste to verify that portion of your logic.