AGITATE phase logic configuration
Verify the AGITATE holding and restarting logic
- Download UM_BLEND_500. If asked, do not accept the online values for uploading. Click Select None, and then proceed with the download.
- Go to the Batch picture in DeltaV Operate.
- Open the UM_BLEND_500 unit module faceplate.
- Load the AGITATE phase and open the phase faceplate and command list.
- Go to the Process picture.
- Send a Start command and wait for AGIT_500 to begin agitating (phase shows Running).
- Send a Hold command to the AGITATE phase.
- Verify that the phase goes to the Held state and that AGIT_500 stops.
- Send a Restart command to the AGITATE phase.
- Verify that the phase transitions back to the Running state and that AGIT_500 resumes agitating.
- When the phase completes, reset the phase to Idle and unload it.