AGITATE phase logic configuration

Verify the AGITATE holding and restarting logic

  1. Download UM_BLEND_500. If asked, do not accept the online values for uploading. Click Select None, and then proceed with the download.
  2. Go to the Batch picture in DeltaV Operate.
  3. Open the UM_BLEND_500 unit module faceplate.
  4. Load the AGITATE phase and open the phase faceplate and command list.
  5. Go to the Process picture.
  6. Send a Start command and wait for AGIT_500 to begin agitating (phase shows Running).
  7. Send a Hold command to the AGITATE phase.
  8. Verify that the phase goes to the Held state and that AGIT_500 stops.
  9. Send a Restart command to the AGITATE phase.
  10. Verify that the phase transitions back to the Running state and that AGIT_500 resumes agitating.
  11. When the phase completes, reset the phase to Idle and unload it.