Smart Commissioning for HART devices

Smart Commissioning enables you to configure control strategies and safety logic using only the Device Signal Tags (DSTs), eliminating the need to define the physical location of the I/O. Each I/O function block is linked to a DST that is not assigned to any particular I/O channel. In a traditional configuration approach, I/O references within control strategies are bound to specific channels, creating unnecessary dependencies in the project schedule. With Smart Commissioning, you can configure HART devices and CHARM properties without defining specific CHARM locations.

You can use I/O Studio to create and configure device placeholders in bulk, and then use DeltaV Device Commissioner to allocate those placeholders appropriately in the control strategy.

Smart Commissioning consists of the following four components:

Smart Commissioning consists of the following DeltaV applications:

Note

Smart Commissioning requires AMS version 14 or later.