User-defined export, import, and bulk editing > Bulk editing configuration objects > Bulk editing a PK controller's Ethernet-connected devices

Ethernet/IP Class 1 Implicit logical device syntax table

Table: Valid field values for Ethernet/IP Class 1 Implicit logical devices

Field

Valid values

Required for import

logical_device_node_name

16 characters or fewer. The string must contain at least one alphabetical character and can include letters, numbers and the following characters: $, -, and _

Yes

physical_device_node_name

16 characters or fewer. The string must contain at least one alphabetical character and can include letters, numbers and the following characters: $, -, and _

Yes

controller_node_name

16 characters or fewer. The string must contain at least one alphabetical character and can include letters, numbers and the following characters: $, -, and _

No

description

Description of logical device

No

messaging_class

Class_1

No

input_size

integer of value 0-500

No

output_size

integer of value 0-500

No

input_assembly_instance

Integer of value 0-65535

No

output_assembly_instance

Integer of value 0-65535

No

requested_packet_interval

Integer of value 50-65535

No

configuration_assembly_id

Integer of value 0-65535

No

protocol

Ethernet/IP

No

connection_priority
  • Low
  • High
  • Scheduled
  • Urgent
No
connection_type
  • Point to point
  • Multicast
No