Field |
Valid Values |
Required for Import |
|---|---|---|
|
description |
As many as 255 characters using any keyboard characters. |
No |
|
node_name |
Any valid node name. |
Yes |
|
card_slot |
1 through 8 |
Yes |
|
card_type |
FIC (fieldbus card) RFIC (redundant fieldbus card) FIC_SER2 (fieldbus card, series 2) |
Yes |
|
redundant |
T = redundant F = not redundant |
Yes |
|
fb_port_slot |
1 through 2 |
Yes |
|
fieldbus_device_tag |
As many as 32 characters. The string must contain one alphabetical character and can include the following: $, -, _ |
Yes |
|
fieldbus_device_address |
20 through 35 |
Yes |
|
fieldbus_device_manufacture |
Derive valid values from the device description. |
Yes |
|
fieldbus_device_type |
Derive valid values from the device description. |
Yes |
|
fieldbus_device_rev |
Derive valid values from the device description. |
Yes |
|
fieldbus_id |
A unique identifier for the fieldbus device |
No |
|
fieldbus_device_bklk_master |
T or F |
No |
|
enable_alarms |
T or F |
No |
|
primary_display |
Any valid picture name |
No |
|
faceplate_display |
Any valid picture name |
No |
|
reannunciation_enable |
T or F |
No |
|
The following fields appear only for fieldbus devices with device alarms. |
||
|
ABNORM_ALM.ENABLE |
T or F |
No |
|
ABNORM_ALM.PRIORITY |
Any valid alarm priority(1) |
No |
|
ADVISE_ALM.ENABLE |
T or F |
No |
|
ADVISE_ALM.PRIORITY |
Any valid alarm priority(1) |
No |
|
COMM_ALM.ENABLE |
T or F |
No |
|
COMM_ALM.PRIORITY |
Any valid alarm priority(1) |
No |
|
FAILED_ALM.ENABLE |
T or F |
No |
|
FAILED_ALM.PRIORITY |
Any valid alarm priority(1) |
No |
|
MAINT_ALM.ENABLE |
T or F |
No |
|
MAINT_ALM.PRIORITY |
Any valid alarm priority(1) |
No |
|
CHKFNC_ALM.ENABLE |
T or F |
No |
|
CHKFNC_ALM.PRIORITY |
Any valid alarm priority(1) |
No |