The following table shows the available fields and valid field values for process cells.
Field |
Valid Values |
Required for Import |
|---|---|---|
description |
As many as 255 characters using any keyboard characters. |
No |
area |
Plant area name may be up to 16 characters long. |
Yes |
proc_cell_class |
Process cell class. |
Yes(1) |
proc_cell_name |
Process cell name. As many as 16 characters. The string must contain one letter and can include the following: $, -, _. |
Yes |
equip_id |
Equipment ID used by the system to acquire and release resources. Valid range: 1 to 65535 |
No |
max_owners |
Specifies the number of requesters that can use this resource simultaneously |
No |
mmi_pic |
Specifies the graphic used to represent this equipment in DeltaV Operate |
No |