Field |
Valid Values |
Required for Import |
|---|---|---|
description |
As many as 255 characters using any keyboard characters |
No |
node_name |
Any valid node name. |
Yes |
card_slot |
1 through 8 |
Yes |
profibus_port_slot |
The slot to which the Profibus port is assigned |
Yes |
enable |
T = enabled F = disabled |
No |
profibus_dev_tag |
As many as 16 characters. This string must contain one alphabetical character and can include the following: $, -, _ |
Yes |
profibus_dev_addr |
The address of the Profibus device |
Yes |
profibus_dev_family |
The family for the device being imported |
Yes |
profibus_dev_manufacturer |
The manufacturer of the Profibus device |
Yes |
profibus_dev_model |
The model of the Profibus device |
Yes |
profibus_dev_revision |
The revision level of the Profibus device |
Yes |
profibus_dev_watchdog_enable |
T = enabled F = disabled |
No |
profibus_dev_watchdog_time |
The time following a communication failure that a device failure action occurs |
No |
Note that for an import or export of a Profibus device to succeed, the Profibus card and Profibus port must already exist.