Field |
Valid Values |
Required for Import |
|---|---|---|
description |
As many as 255 characters using any keyboard characters |
No |
node_name |
Any valid node name. |
Yes |
card_slot |
1 through 8 |
Yes |
card_type |
RED_PROG_SERIAL_32DS (Prog. Serial Card, 2 Ports, RS232/RS485, Redundant) PROG_SERIAL_32DS (Prog Serial Card, 2 Ports, RS232/RS485) PROG_SERIAL_32DS_SER2 (Prog Serial Card, 2 Ports, RS232/RS485, Series 2) |
Yes |
redundant |
T = redundant F = not redundant |
Yes |
device_signal_tag |
16 characters or fewer. This string must contain at least one alphabetical character and can include the following characters: $, -, and _. |
No |
serial_port_slot |
1 or 2 |
Yes |
serial_port_pio_name |
PIO_CFG_NAME_PORT_PROG_SERIAL_RED PIO_CFG_NAME_PORT_PROG_SERIAL |
Yes |
serial_device_index |
1 through 16 |
Yes |
serial_device_description |
As many as 255 characters using any keyboard characters |
No |
serial_device_address |
1 through 16 |
No |
dataset_number |
1 through 16 |
Yes |
dataset_data_direction |
input or output |
No |
dataset_datatype |
Boolean with status Discrete with status 8-bit unit with status 16-bit unit with status 32-bit unit with status 8-bit unit with status 16-bit unit with status 32-bit unit with status Floating point with status String with status |
No |
dataset_num_values |
Dependent on the PLC data type and the DeltaV data type. Refer to the Maximum Number of Values table in the Serial Device Configuration topic. |
No |
dataset_output_mode |
Determines how the serial card transmits output data to the serial device |
No |
dataset_output_readback |
T = Readback the output. F = Do not readback the output. |
No |
device_data_type |
The type of data this dataset contains |
No |
data_start_addr |
0 to 65535 |
No |
special_data1 |
0 to 65535 |
No |
special_data2 |
0 to 65535 |
No |
special_data3 |
0 to 65535 |
No |
special_data4 |
0 to 65535 |
No |
special_data5 |
0 to 65535 |
No |