Field |
Valid Values |
Required for Import |
|---|---|---|
|
description |
As many as 255 characters using any keyboard characters |
No |
|
node_name |
Any valid node name. |
Yes |
|
card_slot |
1 through 8 |
Yes |
|
card_type |
SERIAL_32DS (Serial Card, 2 Ports, RS232/RS485) SERIAL_32DS_SER2 (Serial Card, 2 Ports, RS232/RS485, Series 2) RED_SERIAL_32DS (Serial Card, 2 Ports, RS232/RS485, Redundant) |
Yes |
|
redundant |
T = redundant F = not redundant |
Yes |
|
device_signal_tag |
16 characters or fewer. This string must contain at least one alphabetical character and can include the following characters: $, -, and _. |
No |
|
serial_port_slot |
1 or 2 |
Yes |
|
serial_port_pio_name |
PIO_CFG_NAME_PORT_SERIAL PIO_CFG_NAME_PORT_SERIAL_RED |
Yes |
|
serial_device_index |
1 through 16 |
Yes |
|
serial_device_description |
As many as 255 characters using any keyboard characters |
No |
|
serial_device_address |
1 through 16 |
No |
|
dataset_number |
1 through 16 |
Yes |
|
dataset_data_direction |
input or output |
No |
|
dataset_datatype |
Boolean with status Discrete with status 8-bit int w/status 16-bit int w/status 32-bit int w/status 8-bit uint w/status 16-bit uint w/status 32-bit uint w/status Floating point with status String w/status |
No |
|
dataset_num_values |
Dependent on the PLC data type and the DeltaV data type. Refer to the Maximum Number of Values table in the Serial Device Configuration topic. |
No |
|
dataset_output_mode |
Determines how the serial card transmits output data to the serial device |
No |
|
dataset_output_readback |
T = Readback the output. F = Do not readback the output. |
No |
|
dataset_plc_datatype |
coils input status input registers holding registers diagnostics data |
No |
|
dataset_plc_reg_addr_offset |
0 through 65535 |
No |