The following table shows the available fields and valid field values for unit modules.
Field |
Valid Values |
Required for Import |
|---|---|---|
description |
As many as 255 characters using any keyboard characters. Note that only the first 24 characters appear in faceplates. |
No |
area |
Plant area name may be up to 16 characters long. |
Yes |
unit_mod_class |
Unit class name. The class must already exist in the database. |
Yes(1) |
unit_mod_name |
Unit module name. As many as 16 characters. The string must contain one letter and can include the following: $, -, _. |
Yes |
work_in_prog |
Flag used during configuration to mark a module as being unfinished. T or F |
No |
scan_rate |
Use Select Entry for list of valid entries. |
No |
primary_display |
The primary control display picture name without extension. |
No |
detail_display |
The detail display picture name without extension. |
No |
faceplate_display |
The faceplate display picture name without extension. |
No |
equip_id |
Equipment ID used by the system to acquire and release resources. Valid range: 1 to 65535. |
No |
max_owners |
Specifies the number of requesters that can use this resource simultaneously. |
No |
downstream_unit_selection |
How downstream units are selected. Valid values are: |
No |
downstream_units |
Used on class-based unit modules only. All units in the Downstream list must currently exist in the configuration. |
No |
Parameter List |
Depends on subtype. |
No |